FieldPoint™ Operating InstructionsFP-AI-112 and cFP-AI-11216-Channel, 16-Bit Analog Input ModulesThese operating instructions describe how to install
FP-AI-112 and cFP-AI-112 10 ni.comEffective resolution by input range and filter settingUpdate period and input bandwidth by filter settingNormal-mode
© National Instruments Corp. 11 FP-AI-112 and cFP-AI-112Typical and warranted accuracy by input range and temperature rangeNote Full scale is the maxi
FP-AI-112 and cFP-AI-112 12 ni.comPhysical CharacteristicsIndicators ... Green POWER and READY indicatorsWeight
© National Instruments Corp. 13 FP-AI-112 and cFP-AI-112Shock and VibrationThese specifications apply only to the cFP-AI-112. NI recommends Compact Fi
FP-AI-112 and cFP-AI-112 14 ni.comCE ComplianceThis product meets the essential requirements of applicable European Directives, as amended for CE mark
© National Instruments Corp. 15 FP-AI-112 and cFP-AI-112Where to Go for SupportFor more information about setting up the FieldPoint system, refer to t
© 2004 National Instruments Corp. All rights reserved.371330A-01 Jul04*371330A-01*FieldPoint™, National Instruments™, NI™, and ni.com™ are trademarks
FP-AI-112 and cFP-AI-112 2 ni.comTo install the FP-AI-112, refer to Figure 1 and complete the following steps:1. Slide the terminal base key to either
© National Instruments Corp. 3 FP-AI-112 and cFP-AI-1123. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tight
FP-AI-112 and cFP-AI-112 4 ni.comYou can use an external power supply to power field devices. Connect the positive lead of the external power supply t
© National Instruments Corp. 5 FP-AI-112 and cFP-AI-112Caution Cascading power between two modules defeats isolation between those modules. Cascading
FP-AI-112 and cFP-AI-112 6 ni.comInput RangesThe input ranges for voltage signals are 0–1 V, 0–5 V, 0–10 V, ±60 mV, ±300 mV, ±1V, ±5 V, and ±10 V. To
© National Instruments Corp. 7 FP-AI-112 and cFP-AI-112(number of input ranges with 60 Hz filter) × 0.10 s +(number of channels with 500 Hz filter) ×
FP-AI-112 and cFP-AI-112 8 ni.comIsolation and Safety GuidelinesCaution Read the following information before attempting to connect the [c]FP-AI-112 t
© National Instruments Corp. 9 FP-AI-112 and cFP-AI-112using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. panhead screw shipped with the bac